Wire Size Calculator

Estimate cable cross-section from voltage drop and load — a planning figure, not a compliant selection.

Please note: For planning and educational use only. Electrical installation is governed by wiring regulations and is dangerous when done incorrectly. Always have work designed, installed and inspected by a qualified electrician.

What the Wire Size Calculator does

Cable sizing balances two constraints: the conductor must carry the current without overheating, and it must keep voltage drop within limits over the run. Long runs are usually governed by voltage drop, short runs by current capacity.

Formula

  • Area for voltage drop = Multiplier × I × ρ × Length ÷ Allowable drop
  • Multiplier is 2 for single phase, √3 for three phase
  • Area for capacity ≈ Current ÷ (Capacity per mm² × Derating)
  • Selected size = next standard size above the larger requirement

Inputs explained

InputUnitRequiredNotes
Supply typeone of 2 optionsYes
Conductor materialone of 2 optionsYes
Supply voltageVYesAccepts 0 or more.
Load currentAYesAccepts more than 0.
One-way cable lengthnumberYesAccepts more than 0.
One-way cable length unitone of 6 optionsYes
Maximum voltage drop%Yes
Derating factor%YesReduce for grouping, insulation or high ambient temperature.

How to use it

  1. Choose Supply type and Conductor material.
  2. Enter Supply voltage, Load current, One-way cable length and Maximum voltage drop and 1 more.
  3. Select Calculate.

Worked example

32 A over 25 m of copper on 230 V single phase with a 3% drop limit.

Current
32 A
Length
25 m
Voltage
230
Max drop
3

Allowable drop 6.9 V, required area 3.997 mm², capacity needs 5.33 mm² → select 6 mm², giving a 2.0% drop.

Frequently asked questions

Why did it pick a larger cable than the voltage drop needs?

Because current capacity governed instead. Short runs with heavy loads are limited by heating, not by drop.

Can I use this for a real installation?

No. Use it to understand the trade-offs, then have a qualified electrician design to the actual regulations, which account for far more variables.

Method and sources

Method. Two constraints are computed and the larger governs. Voltage drop uses conductor resistivity, length and current to find the area that keeps the drop within the limit entered. Current-carrying capacity uses a simplified capacity-per-square-millimetre figure with a derating factor. The result is rounded up to the next standard size.

Applies to. None applied — cable sizing is governed by the national wiring regulations in force where the installation is located, and those tables are not shipped here

Assumptions

  • Copper or aluminium at a nominal temperature, with resistivity taken as representative rather than certified for a specific cable.
  • The derating factor entered accounts for installation conditions — the calculator does not derive it.
  • One circuit is considered in isolation, with no grouping effects from adjacent cables.

Limitations

  • HUMAN REVIEW REQUIRED — the current-capacity side is an approximation, not a regulatory figure. Real ampacity is read from tables in the wiring regulations and varies substantially with installation method, grouping, ambient temperature and insulation type. A single capacity-per-square-millimetre figure can indicate a smaller conductor than the tables require, and an under-sized conductor is a fire risk.
  • Nothing here selects a protective device, checks earth-fault loop impedance, verifies disconnection times or considers short-circuit withstand — all of which are required parts of a compliant design.
  • The voltage-drop side ignores reactance, which understates drop on large conductors and long AC runs.
  • This calculator is for planning and estimating only. It is not a cable schedule, and it must not be used to size a conductor for an installation.

Sources

  • The national wiring regulations applying where the installation is located, and their current-carrying capacity tables — Varies by country. The ampacity figures, derating factors, permitted voltage drop and every other input to a compliant design. This calculator approximates the first and applies none of the rest.
  • Conductor resistivity for copper and aluminium — Standard material data; a cable manufacturer's datasheet governs a specific construction. The voltage-drop side of the calculation, which is straightforward physics.

Related calculators